6.3.3 Parameter Group 31-** Flow Protection
Flow protection uses terminals B33, B34 or C23, C24 on the smart card.
Table 9: 31-1 - High Flow Trip Level
Range Function
*10 0–5000 Sets the trip point for high flow protection.
Table 10: 31-2 - Low Flow Trip Level
Range Function
* 5 1–5000 Sets the trip point for low flow protection.
Table 11: 31-3 - Flow Start Delay
Range Function
*00:00:500 ms 00:00:100–
30:00:000
mm:ss:ms
Sets a delay before a flow protection trip can occur. The delay is counted from the time a start
signal is received. The flow level is ignored until the start delay has elapsed.
Table 12: 31-4 - Flow Response Delay
Range Function
* 00:00:500 ms 00:00:100–30:00:000
mm:ss:ms
Sets a delay between the flow passing the high or low flow trip levels, and the soft start-
er tripping.
6.3.4 Parameter Group 36-** Pump Trip Action
Table 13: 36-2 - Flow Sensor
Option Function
Selects the soft starter's response if it detects a fault with the flow sensor.
* Soft Trip and Log
Soft Trip and Reset
Trip Starter
Trip and Reset
Warn and Log
Log Only
Table 14: 36-6 - High Flow
Option Function
Selects the soft starter's response if the flow exceeds the high flow trip level (parameter 31-1 High Flow
Trip Level).
* Soft Trip and Log
Configuration
Installation Guide | Pumping Smart Card
AN279052730268en-000102 / 175R1183 | 15
Danfoss A/S © 2018.10

Table of Contents

Other manuals for Danfoss VLT MCD 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 600 and is the answer not in the manual?

Danfoss VLT MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 600
CategoryController
LanguageEnglish

Related product manuals