Table 35: 33-2 - Start Pressure Level
Range Function
* 5 1–5000 Sets the pressure level to trigger the soft starter to perform a soft start.
Table 36: 33-3 - Start Response Delay
Range Function
* 0.5 s 00:00:100–30:00:000
mm:ss:ms
Sets a delay between the pressure passing the pressure control start level and the soft starter per-
forming a soft start.
Table 37: 33-4 - Stop Pressure Level
Range Function
* 10 0–5000 Sets the pressure level to trigger the soft starter to stop the motor.
Table 38: 33-5 - Stop Response Delay
Range Function
* 0.5 s 00:00:100–30:00:000
mm:ss:ms
Sets a delay between the pressure passing the pressure control stop level and the soft starter
stopping the motor.
6.5.2.5 Parameter Group 36-** Pump Trip Action
Table 39: 36-1 - Pressure Sensor
Option Function
Selects the soft starter's response if it detects a fault with the pressure sensor.
* Soft and Trip Log
Soft Trip and Reset
Trip Starter
Trip and Reset
Warn and Log
Log Only
6.6 Depth Protection
Depth protection uses terminals B13, B14 or C13, C14 on the smart card.
• B13, B14: Use an analog 4–20 mA sensor.
• C13, C14: Use a normally open digital switch sensor.
Depth protection is always active (ready, start, run, and stop modes).
The smart card trips the soft starter when the depth level passes through the programmed trip level. The trip cannot be reset until the
depth has returned above the reset level (parameter 34-2 Depth Reset Level).
Configuration
Installation Guide | Pumping Smart Card
AN279052730268en-000102 / 175R1183
24 | Danfoss A/S © 2018.10