6.6.1.3 Parameter Group 30-** Pump Input Configuration
Table 40: 30-12 - Depth Sensor Type
Option Function
Selects which type of sensor is associated with the depth sensor input on the smart card.
* None
Switch
Analog
Table 41: 30-13 - Depth Units
Option Function
Selects which units the sensor uses to report the measured depth.
* meters
feet
Table 42: 30-14 - Depth at 4 mA
Range Function
*0 0–1000 Calibrates the soft starter to the 4 mA (0%) level of the depth sensor input.
Table 43: 30-15 - Depth at 20 mA
Range Function
*0 0–1000 Calibrates the soft starter to the 20 mA (100%) level of the depth sensor input.
6.6.1.4 Parameter Group 34-** Depth Protection
Depth protection uses terminals B13, B14 or C13, C14 on the smart card.
Table 44: 34-1 - Depth Trip Level
Range Function
* 5 0–1000 Sets the trip point for depth protection.
Table 45: 34-2 - Depth Reset Level
Range Function
* 10 0–1000 Sets the level for the soft starter to allow a depth trip to be reset.
Table 46: 34-3 - Depth Start Delay
Range Function
* 0.5 s 00:00:100–
30:00:000
mm:ss:ms
Sets a delay before a depth protection trip can occur. The delay is counted from the time a start sig-
nal is received. The depth input is ignored until the start delay has elapsed.