5.1.3 Active/Inactive Parameters in Dierent Drive Control Modes
+ indicates that the parameter is active in the mode.
- indicates that the parameter is inactive in the mode.
Parameter 1-10 Motor Construction AC motor
Parameter 1-01 Motor Control Principle
U/f mode
VVC
+
Parameter 1-00 Conguration Mode
[0] Speed Open Loop + +
[1] Speed Closed Loop - +
[2] Torque Closed Loop - +
[3] Process + +
[4] Torque Open Loop - +
[7] Ext. PID Open Loop + +
Parameter 1-03 Torque Characteristics
-
+ see
1, 2, 3)
Parameter 1-06 Clockwise Direction + +
Parameter 1-20 Motor Power [kW]
(parameter 0-03 Regional Settings =[0] International)
+ +
Parameter 1-22 Motor Voltage + +
Parameter 1-23 Motor Frequency + +
Parameter 1-24 Motor Current + +
Parameter 1-25 Motor Nominal Speed + +
Parameter 1-29 Automatic Motor Adaptation (AMA) + +
Parameter 1-30 Stator Resistance (Rs) + +
Parameter 1-33 Stator Leakage Reactance (X1) + +
Parameter 1-35 Main Reactance (Xh) + +
Parameter 1-39 Motor Poles + +
Table 5.3 Active/Inactive Parameters
1) Constant torque
2) Variable torque
3) AEO
Parameter 1-10 Motor Construction AC motor
Parameter 1-01 Motor Control Principle
U/f mode
VVC
+
Parameter 1-50 Motor Magnetisation at Zero Speed - +
Parameter 1-52 Min Speed Normal Magnetising [Hz] - +
Parameter 1-55 U/f Characteristic - U + -
Parameter 1-56 U/f Characteristic - F + -
Parameter 1-60 Low Speed Load Compensation - +
Parameter 1-61 High Speed Load Compensation - +
Parameter 1-62 Slip Compensation
-
+ see
6)
Parameter 1-63 Slip Compensation Time Constant
+ see
7)
+
Parameter 1-64 Resonance Damping + +
Parameter 1-65 Resonance Damping Time Constant + +
Parameter 1-71 Start Delay + +
Parameter 1-72 Start Function + +
Parameter 1-73 Flying Start - +
Parameter 1-75 Start Speed [Hz] - +
Parameter 1-76 Start Current - +
Table 5.4 Active/Inactive Parameters
6) Not used when parameter 1-03 Torque Characteristics=VT.
7) Part of resonance damping.
Parameter Lists