4.12 Parameters: 12-** Ethernet
12-00 IP Address Assignment
Option: Function:
[0] MANUAL Set the IP address in parameter 12-01 IP
Address.
[1] DHCP IP address is assigned via DHCP server.
[2] BOOTP IP address is assigned via BOOTP server.
[10] * DCP
[20] From node ID
12-01 IP Address
Range: Function:
0* [0 -
4294967295 ]
Congure the IP address of the option.
Read-only if parameter 12-00 IP Address
Assignment is set to [1] DHCP, [2] BOOTP,
or via DIP switches.
12-02 Subnet Mask
Range: Function:
0* [0 -
4244635647 ]
Congure the IP subnet mask of the
option. Read-only if parameter 12-00 IP
Address Assignment is set to [1] DHCP or
[2] BOOTP.
12-03 Default Gateway
Range: Function:
0* [0 -
2147483647 ]
Congure the IP default gateway of the
option. Read-only if parameter 12-00 IP
Address Assignment set to [1] DHCP or [2]
BOOTP.
12-04 DHCP Server
Range: Function:
0* [0 - 2147483647 ]
NOTICE
A power cycle is necessary after
setting the IP parameters manually.
Read only. Displays the IP address of the
found DHCP or BOOTP server.
12-05 Lease Expires
Range: Function:
0* [0 - 4294967295 ] Read only. Shows the lease time left for
the current DHCP-assigned IP address.
12-06 Name Servers
Range: Function:
0* [0 - 2147483647] IP addresses of domain name servers. Can
be automatically assigned when using
DHCP.
12-07 Domain Name
Range: Function:
0* [0–48 ] Domain name of the attached network. Can be
automatically assigned when using DHCP network.
12-08 Host Name
Range: Function:
0* [0–48 ] Logical (given) name of option.
12-09 Physical Address
Range: Function:
0* [0–17 ] Read only.
Shows the physical (MAC) address of the option.
12-10 Link Status
Option: Function:
[0] * No Link
[1] Link Shows the link status of the Ethernet ports.
12-11 Link Duration
Range: Function:
Size related* [ 0 - 0 ] Shows the duration of the present link
on each port in dd:hh:mm:ss.
12-12 Auto Negotiation
Option: Function:
Congures auto negotiation of Ethernet link
parameters, for each port: ON or OFF.
[0] O Link speed and link duplex can be congured in
parameter 12-13 Link Speed and parameter 12-14 Link
Duplex.
[1] * On
12-13 Link Speed
Option: Function:
Forces the link speed for each port in 10 Mbps
or 100 Mbps. If parameter 12-12 Auto Negotiation
is set to [1] On, this parameter is read-only and
shows the actual link speed. If no link is present,
None is shown.
[0] * None
[1] 10 Mbps
[2] 100
Mbps
12-14 Link Duplex
Option: Function:
Forces the duplex for each port to full or half
duplex. If parameter 12-12 Auto Negotiation is
set to [1] On, this parameter is read-only.
[0] Half Duplex
[1] * Full Duplex
Parameter Descriptions
VLT
®
Midi Drive FC 280
82 Danfoss A/S © 12/2015 All rights reserved. MG07C102
44

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals