4.4 Parameters: 3-** Reference/Ramps
3-00 Reference Range
Option: Function:
[0] * Min - Max Select the range of the reference signal and
the feedback signal. Signal values can be
positive only, or positive and negative.
[1] -Max -
+Max
For both positive and negative values (both
directions), relative to parameter 4-10 Motor
Speed Direction.
3-01 Reference/Feedback Unit
Option: Function:
Select the unit for process PID control references
and feedbacks.
[0]
[1] %
[2] RPM
[3] Hz
[4] Nm
[5] PPM
[10] 1/min
[12] Pulse/s
[20] l/s
[21] l/min
[22] l/h
[23] m³/s
[24] m³/min
[25] m³/h
[30] kg/s
[31] kg/min
[32] kg/h
[33] t/min
[34] t/h
[40] m/s
[41] m/min
[45] m
[60] °C
[70] mbar
[71] bar
[72] Pa
[73] kPa
[74] m WG
[80] kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
3-01 Reference/Feedback Unit
Option: Function:
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[150] lb ft
[160] °F
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] HP
3-02 Minimum Reference
Range: Function:
0
Reference
Feedback
Unit*
[ 0 - 4999
Reference
Feedback
Unit]
Enter the minimum reference. The
minimum reference is the lowest value
obtainable by summing all references.
The minimum reference is active only
when parameter 3-00 Reference Range is
set to [0] Min.–Max.
The minimum reference unit matches:
The option in
parameter 1-00 Conguration
Mode.
The unit selected in
parameter 3-01 Reference/
Feedback Unit.
3-03 Maximum Reference
Range: Function:
Size
related*
[-4999.0 - 4999
ReferenceFeed-
backUnit]
Enter the maximum reference. The
maximum reference is the highest
value obtainable by summing all
references.
The maximum reference unit
matches:
The option selected in
parameter 1-00 Conguration
Mode.
The unit selected in
parameter 3-00 Reference
Range.
3-04 Reference Function
Option: Function:
[0] * Sum Sums both external and preset reference
sources.
[1] External/
Preset
Use either the preset or the external
reference source. Shift between external and
preset via a command or a digital input.
Parameter Descriptions
VLT
®
Midi Drive FC 280
42 Danfoss A/S © 12/2015 All rights reserved. MG07C102
44

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals