No. Description Warning Alarm Trip lock Cause
53 AMA big motor
– X –
The power size of the motor is too large for the AMA to
operate.
54 AMA small motor
– X –
The power size of the motor is too small for the AMA to
operate.
55 AMA parameter range – X –
The parameter values of the motor are outside of the
acceptable range. AMA does not run.
56 AMA interrupt – X – The AMA is interrupted.
57 AMA timeout – X – –
58 AMA internal – X – Contact Danfoss.
59 Current limit X X – Frequency converter overload.
61 Encoder loss X X – –
63 Mechanical brake low – X –
Actual motor current has not exceeded release brake-
current within start delay-time window.
65 Control card temp
X X X
The cut-out temperature of the control card has
exceeded the upper limit.
67 Option change
– X –
A new option is detected or a mounted option is
removed.
68 Safe Stop
X X –
STO is activated. If STO is in manual restart mode
(default), to resume normal operation, apply 24 V DC to
terminals 37 and 38, and initiate a reset signal (via
eldbus, digital I/O, or [Reset]/[O Reset] key). If STO is in
automatic restart mode, applying 24 V DC to terminals 37
and 38 automatically resumes the frequency converter to
normal operation.
69 Power card temp
X X X
The cut-out temperature of the power card has exceeded
the upper limit.
80 Drive initialised to default value – X – All parameter settings are initialized to default settings.
87 Auto DC braking X – –
Occurs in IT mains when the frequency converter coasts,
and the DC voltage is higher than 830 V for 400 V units,
and 425 V for 200 V units. The motor consumes energy
on the DC link. This function can be enabled/disabled in
parameter 0-07 Auto DC Braking.
88 Option detection – X X The option is removed successfully.
95 Broken belt X X – –
120 Position control fault – X – –
188 STO internal fault
– X –
24 V DC supply is connected to only 1 of the 2 STO
terminals (37 and 38), or a failure in STO channels is
detected. Ensure that both terminals are connected to
24 V DC supply, and that the discrepancy between the
signals at the 2 terminals is less than 12 ms. If the fault
still occurs, contact the local Danfoss supplier.
nw
run
Not while running – – –
Parameter can only be changed when the motor is
stopped.
Err. A wrong password was entered – – –
Occurs when using a wrong password for changing a
password-protected parameter.
Table 6.2 Warnings and Alarms Code List
1) Mains distortions may cause these faults. Installing a Danfoss line lter may rectify this problem.
For diagnosis, read out the alarm words, warning words, and extended status words.
Troubleshooting Programming Guide
MG07C102 Danfoss A/S © 12/2015 All rights reserved. 135
6
6