EasyManuals Logo
Home>Danfoss>DC Drives>VLT Midi Drive FC 280

Danfoss VLT Midi Drive FC 280 Programming Guide

Danfoss VLT Midi Drive FC 280
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #137 background imageLoading...
Page #137 background image
No. Description Warning Alarm Trip lock Cause
53 AMA big motor
X
The power size of the motor is too large for the AMA to
operate.
54 AMA small motor
X
The power size of the motor is too small for the AMA to
operate.
55 AMA parameter range X
The parameter values of the motor are outside of the
acceptable range. AMA does not run.
56 AMA interrupt X The AMA is interrupted.
57 AMA timeout X
58 AMA internal X Contact Danfoss.
59 Current limit X X Frequency converter overload.
61 Encoder loss X X
63 Mechanical brake low X
Actual motor current has not exceeded release brake-
current within start delay-time window.
65 Control card temp
X X X
The cut-out temperature of the control card has
exceeded the upper limit.
67 Option change
X
A new option is detected or a mounted option is
removed.
68 Safe Stop
X X
STO is activated. If STO is in manual restart mode
(default), to resume normal operation, apply 24 V DC to
terminals 37 and 38, and initiate a reset signal (via
eldbus, digital I/O, or [Reset]/[O Reset] key). If STO is in
automatic restart mode, applying 24 V DC to terminals 37
and 38 automatically resumes the frequency converter to
normal operation.
69 Power card temp
X X X
The cut-out temperature of the power card has exceeded
the upper limit.
80 Drive initialised to default value X All parameter settings are initialized to default settings.
87 Auto DC braking X
Occurs in IT mains when the frequency converter coasts,
and the DC voltage is higher than 830 V for 400 V units,
and 425 V for 200 V units. The motor consumes energy
on the DC link. This function can be enabled/disabled in
parameter 0-07 Auto DC Braking.
88 Option detection X X The option is removed successfully.
95 Broken belt X X
120 Position control fault X
188 STO internal fault
X
24 V DC supply is connected to only 1 of the 2 STO
terminals (37 and 38), or a failure in STO channels is
detected. Ensure that both terminals are connected to
24 V DC supply, and that the discrepancy between the
signals at the 2 terminals is less than 12 ms. If the fault
still occurs, contact the local Danfoss supplier.
nw
run
Not while running
Parameter can only be changed when the motor is
stopped.
Err. A wrong password was entered
Occurs when using a wrong password for changing a
password-protected parameter.
Table 6.2 Warnings and Alarms Code List
1) Mains distortions may cause these faults. Installing a Danfoss line lter may rectify this problem.
For diagnosis, read out the alarm words, warning words, and extended status words.
Troubleshooting Programming Guide
MG07C102 Danfoss A/S © 12/2015 All rights reserved. 135
6
6

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals