9.3 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–500 Hz
Output frequency in VVC
+
mode 0–200 Hz
Switching on output Unlimited
Ramp time 0.01–3600 s
Torque characteristics
Starting torque (constant torque) Maximum 160% for 60 s
1)
Overload torque (constant torque) Maximum 160% for 60 s
1)
Starting current Maximum 200% for 1 s
Torque rise time in VVC
+
mode (independent of f
sw
) Maximum 50 ms
1) Percentage relates to the nominal torque. It is 150% for 11–22 kW (15–30 hp) frequency converters.
9.4 Ambient Conditions
Ambient conditions
Enclosure protection rating, frequency converter IP20 (IP21/Type 1 as option)
Enclosure protection rating, conversion kit IP21/Type 1
Vibration test, all enclosure sizes 1.14 g
Relative humidity 5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Ambient temperature (at DPWM switching mode)
- with derating Maximum 55 °C (131 °F)
1)2)3)
- at full constant output current Maximum 45 °C (113 °F)
4)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)
Minimum ambient temperature at reduced performance -10 °C (14 °F)
Temperature during storage/transport -25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating 1000 m (3280 ft)
Maximum altitude above sea level with derating 3000 m (9243 ft)
EMC standards, emission
EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
EN 61000-3-12, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61326-3-1
Energy eciency class
5)
IE2
1) Refer to Special Conditions in the design guide for:
Derating for high ambient temperature.
Derating for high altitude.
2) To prevent control card overtemperature on PROFIBUS, PROFINET, EtherNet/IP, and POWERLINK variants of VLT
®
Midi Drive FC
280, avoid full digital/analog I/O load at ambient temperature higher than 45
°
C (113
°
F).
3) Ambient temperature for K1S2 with derating is maximun 50
°
C (122
°
F).
4) Ambient temperature for K1S2 at full constant output current is maximun 40
°
C (104
°
F).
5) Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
Open type: Surrounding air temperature 45
°
C (113
°
F).
Type 1 (NEMA kit): Ambient temperature 45
°
C (113
°
F).
Specications
VLT
®
Midi Drive FC 280
56 Danfoss A/S © 10/2017 All rights reserved. MG07A402
99

Table of Contents

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals