When this Mode is turned on, inverter will maintain power factor as a constant
value. Users can set power factor from Cap 0.80 to Ind 0.80.
5.3.7.4.3 Constant cosφ
Figure 5-20 : Constant cosφ setting page
Active/Reactive Power
21. Jun 2010 13:50
Constant cosφ
cosφ(P)
Constant Reactive Power
Q(V)
Reactive Power Control
21. Jun 2010 13:50
cosφ 1.00[ ]
Mode OFF[ ]
EXIT
ENT
The inverter controls the output cosφ as a function of the power it injects into the
utility mains and cosφ (P) control will not concern Grid voltage.
5.3.7.4.4 cosφ(P)
Figure 5-21 : cosφ(P) setting page
Active/Reactive Power
21. Jun 2010 13:50
Constant cosφ
cosφ(P)
Constant Reactive Power
Q(V)
Reactive Power Control
21. Jun 2010 13:50
Lower limit - cosφ
Upper limit - cosφ Cap 0.90
Ind 0.90
[
[
]
]
Lower Power 0[ ] %
Upper Power 100[ ] %
Lock-in Voltage - -[ ] V
Lock-out Voltage [ ]
Reactive Power Control
21. Jun 2010 13:50
Mode OFF[ ]
- -
V
Lock-out Voltage
[ ]
EXIT
ENT
a
b
c
d
a
b
c
d
Upper
Limit
Upper
Power
Lower
Power
cosφ
P/Pn
1
Lower
Limit
59