Type of Equipment
Appendix
Appendix A: Type of Equipment
Model
Absolute maximum
PV input voltage
Operation voltage range
Maximum power MPPT range
MPPT accuracy
Inverter wake up voltage
1100Vdc
> 1000Vdc, INV Stop
520Vdc – 1000Vdc
550Vdc – 850Vdc
C1000
> 99.9% at rated power
> 200Vdc (Aux-power on)
Startup voltage 570Vdc
MPP tracker 1
Input current limitation 2050A
Input detection tolerance Input voltage deviation < 2%
DC breaker 250A×14 Runs
Input protection
DC over voltage_electronic shutdown
DC current limitation_current control
Surge arrestor_1100V/40kA Type 2
Maximum input short circuit current 2500A
Output
Output capacity
Grid
Utility voltage range
Utility frequency
Utility frequency range
1000kW / 1000kVA
Three phase (3P3W-IT)
350VΔ ±10%
50/60Hz
Domestic regulation (Max 50/60Hz ± 5Hz)
Maximum output current 1650A
Anti-islanding Domestic regulation
Output reconnect
Connect to utility after utility recover and
countdown finished
Reconnect time Domestic regulation
Input
76
Appendix A: Type of Equipment