Chapter 16 PLC Function ApplicationsC2000 Plus
16-154
16-10 Internal communications main node control
The protocol has been developed in order to facilitate the use of RS-485 instead of CANopen in certain
application situations. The RS-485 protocol offers similar real-time characteristics as CANopen. The
maximum number of slave devices is 8.
Internal communications have a master-slave structure. The initiation method is very simple:
Slave device:
Set Pr. 09-31 = -1 to -8 in order to access 8 nodes, and set Pr. 00-20 = 1 to define the control source
as RS-485 and access the reference sources that must be controlled, namely speed command (Pr.
00-21 = 2), torque command (Pr. 11-33 = 1), and position command (Pr. 11-40=2). This will complete
slave device settings. (PLC functions do not need
to be activated)
System
Setting the master is even simpler; it is only necessary to set Pr. 09-31 = -10, and enable the PLC.
Hardware wiring: The master and slave stations are connected via the RS-485 serial port. The C2000
Plus provides two types of RS-485 serial port interfaces, see the figure below: (please refer to Chapter
06 “Control Terminals” concerning detailed terminal connections)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals