Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-05-1
05 Motor Parameters
The following are abbreviations for different types of motors:
IM: Induction motor
PM: Permanent magnet synchronous AC motor
IPM: Interior permanent magnet synchronous AC motor
SPM: Surface permanent magnet synchronous AC motor
SynRM: Synchronous reluctance motor
You can set this parameter during operation.
05-00
Motor Parameter Auto-Tuning
Default: 0
Settings 0: No function
1: Simple rolling auto-tuning for induction motor (IM)
2: Static auto-tuning for induction motor (IM)
4: Dynamic test for PM magnetic pole (with the running in forward direction)
5: Rolling auto-tuning for PM (IPM / SPM)
6: Advanced rolling auto-tuning for IM
11: Static auto-tuning for SynRM
12: FOC sensorless inertia estimation
13: Static auto-tuning for PM
Refer to Section 12-2 “Adjustment and Application” for more details of motor adjustment
process.
05-01
Full-Load Current for Induction Motor 1 (A)
Default: Depending on the
model power
Settings Depending on the model power
Set this value according to the rated current of the motor as indicated on the motor nameplate.
The default is 90% of the drive’s rated current.
Example: The rated current for a 7.5 HP (5.5 kW) is 25 A. The default is 22.5 A.
The setting range is between 40%–120% of the rated current.
(25 × 40% = 10 A and 25 × 120% = 30 A)
05-02
Rated Power for Induction Motor 1 (kW)
Default: Depending on the
model power
Settings 0.00–655.35 kW
Set the rated power for motor 1. The default is the drive’s power value.
05-03
Rated Speed for Induction Motor 1 (rpm)
Default: Depending on the
motor’s number of poles
Settings 0–xxxx rpm
Set the rated speed for the motor as indicated on the motor nameplate.