Chapter 17 Safe Torque Off Function | C2000 Plus
17-9
17-6 New Error Code for STO Function
06-17
Fault Record 1
06-18
Fault Record 2
06-19
Fault Record 3
06-20
Fault Record 4
06-21
Fault Record 5
06-22
Fault Record 6
Default: 0
Settings 72: STO loss 1 (STL1)
76: Safe torque off (STO)
77: STO loss 2 (STL2)
78: STO loss 3 (STL3)
Error Code Name Description
76
(STO)
STO Safe Torque Off function active
72
(STL1)
STL1
(STO1–SCM1)
STO1–SCM1 internal hardware detect error
77
(STL2)
STL2
(STO2–SCM2)
STO2–SCM2 internal hardware detect error
78
(STL3)
STL3 STO1–SCM1 and STO2–SCM2 internal hardware detect error
The old / new control board and old / new I/O card:
C2000 v1.12 firmware v1.20 firmware
v1.12 control board + old I/O card (no STO function) OK OK
v1.12 control board + new I/O card (with STO function) Error Error
v1.20 control board + old I/O card (no STO function) Error Error
v1.20 control board + new I/O card (with STO function) Error OK

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals