Appendix A. Modbus ProtocolC2000 Plus
A-8
A-4 Address list
1. ASCII
Reads one or more parameter values: 3Ah (start bit‘’) + 30h 31h (station address 01) + 30h
33h (function code 03h) + 30h 30h xxh xxh–32h 36h xxh xxh (Modbus address 00xxh–26xxh)
+ xxh xxh xxh xxh (reading length 1) + LRC (checksum) + CR/LF
Writes one parameter value: 3Ah (start bit‘’) + 30h 31h (station address 01) + 30h 36h
(function code 06h) + 30h 30h xxh xxh–32h 36h xxh xxh(Modbus address 00xxh–26xxh) +
xxh xxh xxh xxh (writing value) + LRC (checksum) + CR/LF
Writes 20 parameter values: 3Ah (start bit‘’) + 30h 31h (station address 01) + 31h 30h
(function code 10h) + 30h 30h xxh xxh–32h 36h xxh xxh (Modbus address 00xxh–26xxh) +
30h 30h 31h 34h (word data length) + 32h 38h (byte data length) + xxh xxh xxh xxh (the first
writing value) + ... + xxh xxh xxh xxh (the 20th writing value) + LRC (checksum) + CR/LF
2. RTU
Reads one or more parameter values: 01h (station address 01) + 03h (function code 03h) +
00xxh–26xxh (Modbus address) + xxxxh (reading length) + CRC (checksum)
Writes one parameter value: 01h (station address 01) + 06h (function code 06h) + 00xxh–
26xxh (Modbus address) + xxxxh (writing value) + CRC (checksum)
Writes 20 parameter values: 01h (station address 01) + 10h (function code 10h) + 00xxh–
26xxh (Modbus address) + 0014h (data length, count by word) + 28h (data length, count by
byte) + xxxxh (the first writing value) + ... + xxxxh (the 20th writing value) + CRC (checksum)
3. AC motor drive parameters (GGnnH): communication station address is Pr.09-00 setting value
Modbus
Address
Attribute (Function Code) Description
GGnnH R(03H) / W(06H, 10H)
GG means parameter group, nn means parameter number. For
example, the Modbus address of Pr.04-10 is 040AH when
reading by Delta VFDsoft.
4. Control command (20xx): communication station address is Pr.09-00 setting value
Function
Name
Modbus
Address
Attribute
(Function
Code)
Size Description
Operation
command
2000H
R (03H) /
W (06H,
10H)
U16 bit1~0
00B: No function 1. Remains the status
specified by a first
command until a
second command is
received.
2. Valid only when
operation command
source is set to
communication
(Pr.00-03=2).
01B: Stop
10B: Run
11B: JOG + Run
U16
bit3~2 Reserved
bit5~4
00B: No function
01B: FWD
10B: REV
11B: Change direction
bit7~6
00B: 1st accel. / decel. 1. Valid only when 2000h
bit12 is set to 1.
2. Obtain the current
running speed by
reading 2107h.
01B: 2nd accel. / decel.
10B: 3rd accel. / decel.
11B: 4th accel. / decel.
bit11~8
0000B: zero step speed
0001B: 1st step speed

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals