Chapter 1 IntroductionC2000 Plus
1-6
1-5 RFI Jumper
(1) The drive contains Varistors / MOVs that are connected from phase to phase and from phase to
ground to prevent the drive from unexpected stop or damage caused by mains surges or voltage
spikes. Because the Varistors / MOVs from phase to ground are connected to ground with the RFI
jumper, removing the RFI jumper disables the protection.
(2) In models with a built-in EMC filter, the RFI jumper connects the filer capacitors to ground to form a
return path for high frequency noise in order to isolate the noise from contaminating the mains power.
Removing the RFI jumper strongly reduces the effect of the built-in EMC filter. Although a single drive
complies with the international standards for leakage current, an installation with several drives with
built-in EMC filters can trigger the RCD. Removing the RFI jumper helps, but the EMC performance of
each drive is no longer guaranteed.
Frame AC Screw Torque: 8–10 kg-cm / (6.98.7 lb-in.) / (0.8–1.0 Nm)
Loosen the screws and remove the RFI jumper (as shown below).
Tighten the screws again after you remove the RFI jumper.
Figure 1-5 Figure 1-6
Frame D0H
Remove the RFI jumper by hands (as shown below).
Figure 1-7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Plus Series
CategoryDC Drives
LanguageEnglish

Related product manuals