Page #1244 background image
Appendix A. Modbus ProtocolC2000 Plus
A-3
(7, O, 1)
Odd
parity
Start
bit
01234
5
6
Stop
bit
7-data bits
10-bits character frame
11-bit character frame (For RTU):
(8, N, 2)
Start
bit
0
12
3456
Stop
bit
8-data bits
11-bits character frame
Stop
bit
7
(8, E, 1)
Start
bit
0
12
3456
Stop
bit
8-data bits
11-bits character frame
7
Even
parity
(8, O, 1)
Start
bit
01
2
3456
Stop
bit
8-data bits
11-bits character frame
7
Odd
parity
A-3 Communication Protocol
1. Communication data frame
ASCII mode:
STX Start character = ‘:’ (3AH)
Address High
Communication address:
one 8-bit address consists of 2 ASCII codes
Address Low
Function High
Command code:
one 8-bit command consists of 2 ASCII codes
Function Low
DATA (n-1)
Contents of data:
n x 8-bit data consists of 2n ASCII codes
n 16, maximum of 32 ASCII codes (20 sets of data)
…….
DATA 0
LRC Check High
LRC checksum:
one 8-bit checksum consists of 2 ASCII codes
LRC Check Low
END High
End characters:
END1= CR (0DH), END0= LF(0AH)
END Low

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)