Chapter 7 Optional AccessoriesC2000 Plus
7-90
Choose suitable motor cable and precautions
Improper installation and choice of motor cable will affect the performance of EMC filter. Be sure to
observe the following precautions when selecting motor cable.
1. Use the motor cable with copper braid shielded wire (double shielded is better). The copper braid
shielded wire on the both ends of the motor cable must ground with the shortest distance and the
maximum contact area.
2. Remove the protective painting where the metal plate fixes with the two-hole straps. This is for ensuring
a good contact. See Figure 7-76.
3. Correctly connect the copper braid shielded wire of the motor cable with the metal plate. Use two-hole
straps to fix both ends of copper braid shielded wire of the motor cable on the metal plate. See Figure
7-77.
Figure 7-76
Figure 7-77