3.3.1 AC Grid Types and Connections
The use of a Neutral (N) conductor is optional and depends the grid type and upon
local codes. The default AC Grid connection is 3Ø-3W. If a neutral is required,
this setting must be changed to 3Ø-4W via the front panel controls. The inverter
will operate from the following grid connections without need of an external
transformer:
Grid Type
480V/277V/ 3Ø-4W/Yg,
480V/277V/ 3Ø-4W/Y
480V/3Ø-3W/∆ (ungrounded)
ATTENTION
Inverter connection
3W or 4W +EGC
3W + EGC
3W +EGC
3.3.2 Required Protective Devices for M80U / M60U
North American electrical codes require a dedicated over-current device such
as a circuit breaker in line between the inverter and AC source.
Model Upstream circuit breaker
M80U 125A
M60U 100A
3.3.3 AC wiring preparation (all models)
Below is the procedure for preparing the AC conductors for connection to the
AC terminals (all versions):
Ensure the AC conductors used are sized to the correct ampacity per NEC or
other local code. Refer to Figure 3-17.
• Strip off all wires for 14 mm [0.55in].
• The cross-sectional area for each AC conductor is 1~2/0 AWG.
• Please use the AC cable with temperature rating 90 °C or higher.
Figure 3-17: Size for AC conductors
L1
L2
L3
N
PE
Stripping length:
14 ~16mm [0.55~0.63in]
Conductor cross-section:
1~2/0 AWG (35 ~ 50mm²)
Conductor cross-section:
1~2/0 AWG (35 ~ 50mm²)
Conduit
to/from
AC Grid
39