EasyManuals Logo
Home>Delta>Inverter>M80U

Delta M80U User Manual

Delta M80U
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
DANGER : ELECTRICAL HAZARD!!
- PV array converts sunlight into electric power with high DC voltage and high
DC current which can cause dangerous electrical shock hazard!
- Use an opaque material to cover the PV array before wiring or cabling.
- Ensure the correct polarities are connected when DC cabling is applied.
WARNING !
- The risk of electric shock and fire exists because of high DC and AC voltages.
- Use only PV modules that are UL Listed to1000V or higher.
- Ensure the two DC switches are placed in the "OFF" position, and the PV array
is disconnected when DC conductors are connected.
- The PV Array current carrying conductors (positive or negative) must not be
referenced to ground.
ATTENTION
3.4 Electrical Installation for DC Wiring
- In order not to damage the components in the inverter, don’t repeat to change
the status of DC Switch quickly, the correct operation is waiting for the LCD
display show ”No DC” or turn on the switch after 1 minute later.
CAUTION: DC SWICH ON/OFF !
ATTENTION
duct seal
EMT
Please seal the conduit from inside
the wiring box by using duct seal to
prevent living creature or moisture
enter the wiring box.
47
Installation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta M80U and is the answer not in the manual?

Delta M80U Specifications

General IconGeneral
BrandDelta
ModelM80U
CategoryInverter
LanguageEnglish

Related product manuals