Please read the following instructions for DC wiring (M80/60U_121) :
These models are designed to be utilized with external combiner boxes and are
not provisioned with internal DC combining capability.
Specific size of DC conductors must be determined from NEC or other local codes.
Ensure the correct conductor is connected to its associated terminal with ring lug
(max width 25mm).
The range of conductor sizes accommodated by each DC terminal is 1~3/0AWG.
Tighten each terminal with screw (M6) with a torque value of 52 lbf-in (5.9 Nm).
• For aluminum cable :
Min./max. Conductor cross-section 35 / 70 mm
2
Tightening torque 52 lbf-in (5.9 Nm)
For the 121 model, two mounting options for installing the DC connection are
available, bottom (2" chassis access hole (KO)) or side entry (2½" chassis access
hole (KO)). If side entry is required, remove the bus bar with torque value 159.3
lbf-in (18 Nm) as shown in Figure 3-30. After removing the bus bar, if the bottom
entry is again required, install the bus bar back with torque value 159.3 lbf-in (18 Nm).
3.4.2 DC Wiring Installation for M80/60U_121 models
- Please follow the following guideline for cabling if you use aluminum cables.
Guideline for aluminum conductor :
- The oxide layer must be removed from the surface of the stripped aluminum
conductor.
- The stripped aluminum conductor is greased with Vaseline or contact grease
with comparable properties after oxide layer removed.
- Tightened with the maximum tightening torque for the modular terminal block.
- The installation location must be kept free from humidity or aggressive
atmospheres.
ATTENTION
IN1 +
IN2 +
IN1
-
IN2
-
PE
Conductor cross-section: 1 ~ 3/0 AWG (35 ~ 70mm²)
Allowable PE conductor size 6 ~ 4 AWG (14 ~ 22mm²)
Torque terminal screw to 26 lbf-in (3 Nm)
EMT
Figure 3-27: Size for DC conductors for M80/60U_121