- When 20A string fuses are utilized do not use input 3 or input 6 on
either MPPT channel.
CAUTION !
Input 1 Fuse holders Input 2 Fuse holders
+01 +02 +03 +04 +05 +06
+07 +08
-
01
-
02
-
03
-
04
-
05
-
06
-
07
-
08
+01 +02 +03 +04 +05 +06
+07 +08
-
01
-
02
-
03
-
04
-
05
-
06
-
07
-
08
M80U_120 version is compatible with 1000V/20A UL listed fuse, however, the
designer must be beware of the following requirements:
•
The max Isc-stc of a connected array (sum of all paralleled strings) cannot exceed
the rated Isc limit of the inverter, that is no more than 108A/input or 216A total.
• Because of internal current limitations and higher string currents allowable with
20A fuses, inputs 3 and 6 must not be used.
Figure 3-26: Prohibited fuse location using 20A fuse
IN 1 IN 2IN 1 IN 2
--
-- --
++
++ ++
--
++
--
++
--
++