Chapter 4 Parameters|VFD-EL-W
40
8: Display the setting value and the feedback of PID
control (P)
9: Display AVI analog input terminal signal (V) (I)
10: Display ACI analog input terminal signal (mA/V)
(i)
11: Display IGBT temperature (°C) (h)
User-Defined Coefficient K
Parameter Protection
Password Input
0–9999
0–4: the number of password attempts allowed
Parameter Protection
Password Setting
0–9999
0: No password protection or password is entered
correctly (Pr.00.08)
1: Password has been set
0: V/F voltage frequency control
1: Vector control
50 Hz Power System Base
Voltage Setting
0: 230V/ 400V
1: 220V/ 380V
User-Defined Value
(corresponds to Max.
operation frequency
Pr.01.00)
Decimal Places for User-
Defined Value
Output Phase Order
Selection
0: Standard
1: Reverse the operation direction
Prohibit Write EEPROM
Function
0: Disable
1: Enable, control via MI terminal
2: Enable, MI terminal is invalid