Modbus Offset Register Description
44599 4598 CT Phase Shift All CT Phase Shift X 100 +/-
Writes same value to Registers 50199, 50299, &
50399
44600 4599 CT Integer All Integer value of all CTs, Writes same value to
Registers 50100, 50200, & 50300
44601 4600 CT Decimal All Decimal value of all CTs, Writes same value to
Registers 50100, 50200, & 50300
44602 4601 Data Scalar
A Value of 0-6 that changes the scaling of certain
registers
44603 4602 Demand Window Size Demand window size in minutes; default is 15 min
44604 4603 Volts Multiplier Integer Multiply volts values by this scalar + Volts Multiplier
Decimal/1000. Use with Step-down Transformer.
Affects all parameters that use volts (i.e., kW)
44616 4615 Volts Multiplier Decimal Multiply volts values by (this scalar/1000+Volts
Multiplier Integer). Use with Step-down Transformer.
Affects all parameters that use volts (i.e., kW)
44605 4604 Amps Multiplier Multiply amps value by this scalar. For use with x:5A
CTs and single let monitoring of a three phase load.
Affects all parameters that use amps (i.e, kW)
44606 4605 Communication Setting Baud: 900=9600, 1900=19200, 3800=38400,
5700=57600, 7600 =76800, 11500=115200
Parity: Add 00 = NO, Add 10 = ODD, Add 20 = EVEN
Stop bit: Add 0 = 1 (UART does not permit 0 stop bits),
Add 1 = 1, Add 2 = 2
E.g., 901 = 9600 baud, no parity, 1 stop bit
44607 4606 Service Type A value of 0x0001 configures the meter for DELTA
A value of 0x0000 configures the meter for WYE
44609 4608 Set Line Frequency Line frequency setting for metering: 50=50 Hz,
60=60Hz
44610 4609 Snap Rog Threshold “Snap to Zero” threshold Rogowski CTs. Register value
is:
44611 4610 Snap Volt Threshold “Snap to Zero” threshold for voltage. Register value is
1x:
44612 4611 Communications Settings Write 1833 to change to BACnet mode
50100 10099 CT1 Integer Integer part of CT1
50101 10100 CT1 Decimal Fractional part of NV_CT1
50125 10124 CT1 Type Select 1=mV or 2=Rogowski CT1s
50199 10198 CT1 Phase Shift Phase Shift X 100 +/-
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DENT Instruments powerscout 3037 and is the answer not in the manual?

DENT Instruments powerscout 3037 Specifications

General IconGeneral
BrandDENT Instruments
Modelpowerscout 3037
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals