60
ALL THINGS MODBUS
DEVICE REGISTERS
Modbus Offset Register Description
44201 4200 Model Number 1
st
2 bytes Model Name 10 bytes (ASCII Alpha-Numeric)
44202 4201 Model 2 “
44203 4202 Model 3 “
44204 4203 Model 4 “
44205 4204 Model Number last 2 bytes “
44206 4205 Serial Number 1
st
2 bytes Serial Number 10 bytes (ASCII Alpha-Numeric)
44207 4206 Serial 2 “
44208 4207 Serial 3 “
44209 4208 Serial 4 “
44210 4209 Serial Number last 2 bytes “
44511 4510 Hardware ID Hardware revisions.
44069 4068 Firmware Major Revision Major Revision Level (big software releases)
44070 4069 Firmware Minor Revision Minor Revision Level (small software changes)
CONFIGURATION REGISTERS
Modbus Offset Register Description
40129 0128 Synchronize Register Multiple PowerScout’s synchronization register
44066 4065 Clear Accumulated
Measurements
Writing 1234 resets all 'H' registers, accumulated
PowerScout data (kWh, kWh, etc) stored in flash to
CAM Default value
44525 4524 CT Type All Writes same type for all CTs: 1=MilliVolt, 2=Rogowski
44526 4525 Slave ID !1=DENT, 1=Veris; Sets SLAVE_ID to Veris or DENT