c. Select a Probe type from the drop-down:
l DMP (DMP-SI-485 wired)
l DMP AEF (DMP-SI probe with AEF)
l DMP DENSITY (DMP-SI with density float)
l DMP DENSITY & AEF FLOAT (DMP-SI with density float & AEF)
l XMT/XSI (XMT-SMT / XMT-SI-485)
l XMT/XSI AEF (XMT-SMT / XMT-SI-485)
l XMT/XSI AEF RF (XMT-SMT / XMT-SI-RF with AEF)
l XSI RF
d. Select the product type from the Product family drop-down.
e. Offset product: This value is used to calibrate the position of the product float. Possible
value range: ±5000 mm (197 in).
f. Offset water: This value is used to calibrate the water float Possible value range: ±5000
mm (197 in).
g. Water Min Float Level: This is the threshold to set the water volume at zero and show
the water level.
l If “Water level from probe + water offset” > Water Min Float level, the Water volume
and Water level will be shown.
l If “Water level from probe + water offset” < Water Min Float level, the Water volume will
not be shown but the Water level will be shown.
h. The Tank groups show read-only information that identifies:
l The name of the tank group of which the selected tank is a member.
l A list of all of the tanks in the tank group.
i. Click Save when you complete the Settings configuration.
M2051-EU Rev.: 1 Dover Fueling Solutions
Page 32