P-164000341 8-10 kVA, 50/60 Hz (1-phase input) &
8-15 kVA, 50/60 Hz (3-phase input)
89
Revision 1 User's Guide
UPS 8 kVA 10 kVA 12 kVA 15 kVA
32 battery and transformer: 243 kg 32 battery and transformer: 243 kg
TA models: +20kg TA models: +20kg
MBS Rear mounted MBS: +15 kg
Colour RAL 7035
Table 14-3: Mechanical configuration
Characteristics
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Efficiency
(Nominal load)
Up to 92% Up to 93% Up to 92% Up to 93%
Heat losses <580 W <720 W <870 W <1050 W
Backup time with
internal batteries
(Load pf 0.7
(+25°C amb.)
Backup time can
be extended with
external battery
cabinets.
10 min
(32 bat 7 Ah)
15 min
(32 bat 9 Ah)
28 min
(64 bat 7 Ah)
33 min
(64 bat 9 Ah)
6 min
(32 bat 7 Ah)
10 min
(32 bat 9 Ah)
20 min
(64 bat 7 Ah)
25 min
(64 bat 9 Ah)
8 min
(32 bat 9 Ah)
15 min
(64 bat 7 Ah)
20 min
(64 bat 9 Ah)
5 min
(32 bat 9 Ah)
10 min
(64 bat 7 Ah)
15 min
(64 bat 9 Ah)
Noise (ISO 7779) 50 - 53 dB(A) depending on the load
Table 14-4: Characteristics
The represented Efficiency and Heat loss values are for models without transformers.
AC input
UPS 8 kVA 10 kVA 12 kVA 15 kVA
S/ST/SC model: 1-phase (2-phase) Rectifier input
N/NT/NC model: 3 phases 3 phases 3 phases
Bypass input
(9155): 1-phase (2-phase)
(9355): 3-phase