EasyManuals Logo
Home>Eaton>UPS>93PR Series

Eaton 93PR Series User Manual

Eaton 93PR Series
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
81
Copyright © 2022 Eaton Corporation plc. All rights reserved.
8.2.4. Battery specications
CAUTION! In case of connection with external battery, battery N wire must be included.
Battery type VRLA, 12 Vdc
Battery voltage range 320V–607V
Charging conguration ABM or oat charge
Discharge end off voltage 1.67VPC
Charging current
Congurations:
15kVA max. 15A, congurable
20kVA max. 20A, congurable
30kVA max. 30A, congurable
40kVA max. 40A, congurable
60kVA max. 60A, congurable
80kVA max. 80A, congurable
Battery startup Available
Battery environment
D
ischarging: -20 –+50
Charging: 0 –+40
Storage: -15 –+40
Recommended operating and storage temperature: +25
8.2.5. Environment
Operating ambient temperature
0–40 , the recommended operating temperature is 25 ;
the use shall be derated at 40–50 .
Storage ambient temperature
-25 –55 (-13 –131 ) (placed in the protective
packaging materials)
Operating altitude
The UPS works normally below the altitude of 1,000m
(3,300ft). If you intend to use it at an altitude above 2,000m
(6,600ft), please call Eaton's hotline for more information.
Relative humidity (storage and
operating)
5%–95%, condensation free
A difference of at least 1 Celsius degree (1.8 degrees
Fahrenheit) shall be kept between the dry bulb temperature
and wet bulb temperature of the hygroscope to avoid
condensation.
Noise @1m
Within a distance of 1m:
20k: 61dB;
30k-40k: 66dB;
60k-80k: 68dB, per ISO 7779
EMC
Class: C3 (GB 7260.2 / IEC 62040-2)
Recommended storage environment and storage time of the overall equipment and spare parts:
Equipment which cannot be installed and energized immediately shall be stored indoor, and
in an environment that is clean and well ventilated and that the temperature and humid-
ity are controlled. The storage area must be protected from rain, water, chemicals and the
ambient gases provided in
Table 8-1
, and meet the requirements (see
Table 8-2
) on the
transportation and storage environment for 1 year.

Table of Contents

Other manuals for Eaton 93PR Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 93PR Series and is the answer not in the manual?

Eaton 93PR Series Specifications

General IconGeneral
BrandEaton
Model93PR Series
CategoryUPS
LanguageEnglish

Related product manuals