The working environment of the UPS shall meet the weight and size requirements provided in
Table 3-1
.
When ignored, either one of these aspects can create an undesirable microclimate at the UPS
location. If the environment created by this microclimate exceeds the Eaton UPS operating
specication, the UPS reliability, over time, will be reduced. These same environmental extremes
will also create reliability concerns for any servers that are exposed to them.
The UPS system installation must meet the following guidelines:
• The system must be installed on a level oor suitable for computer or electronic equipment.
The oor must be suitable for heavy weight and wheeling.
• The system must be installed in a temperature and humidity controlled indoor area free of
conductive contaminants.
• The cabinet can be installed in line-up-and-match or standalone congurations.
The UPS equipment operating environment must meet the weight requirements shown in
Table 3-1
.
Table 3-1: Dimensions and Weights
Description
Packaging size
(WxHxD)
Cabinet dimensions
(WxDxH)WxDxH)
Gross
weight
Net
weight
15kVA 440 x 736 x 770 mm 330 x 528 x 657 mm 50kg 40kg
20kVA 440 x 736 x 770 mm 330 x 528 x 657 mm 50kg 40kg
30kVA 440 x 736x 770 mm 330 x 528 x 657 mm 54.5kg 44.5kg
40kVA 440 x 736 x 770 mm 330 x 528 x 657 mm 55kg 45kg
60kVA 560 x 1205x 860 mm 330 x 985.5 x 690 mm 132.5kg 96.5kg
80kVA 560 x 1205x 860 mm 330 x 985.5 x 690 mm 133.5kg 97.5kg
*:As the UPS cabinet controls the temperature of internal components by forced cooling, sufcient space shall be
reserved to ensure sound air circulation. Please see
Figure 3-1
for the method of heat radiation. Please see
Table 3-2
for the reserved space.