Appendix A
172 M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Fixed Frequencies
PNU ID
Access
Designation Value Range Page
FS
(P1.3)
User
SettingRUN ro/rw
P10.1 124 rw Fixed frequency FF0 0.00–P6.4 Hz 101 6.00
P10.2 105 rw Fixed frequency FF1 0.00–P6.4 Hz 101 12.00
P10.3 106 rw Fixed frequency FF2 0.00–P6.4 Hz 101 18.00
P10.4 126 rw Fixed frequency FF3 0.00–P6.4 Hz 101 24.00
P10.5 127 rw Fixed frequency FF4 0.00–P6.4 Hz 101 30.00
P10.6 128 rw Fixed frequency FF5 0.00–P6.4 Hz 101 36.00
P10.7 129 rw Fixed frequency FF6 0.00–P6.4 Hz 101 48.00
P10.8 130 rw Fixed frequency FF7 0.00–P6.4 Hz 101 60.00
P10.9 1436 rw PLC Sequence control,
operating mode
0 = Deactivated
1 = Program cycle, execute once
2 = Execute program cycle continuously
3 = Execute program cycle in steps
4 = Execute program cycle continuously
in steps
102 0
P10.10 1437 rw PLC Sequence control,
program (FWD/REV)
0–255 102 0
P10.11 1438 rw Set time for FF0 0–10000s 103 0
P10.12 1439 rw Set time for FF1 0–10000s 103 0
P10.13 1440 rw Set time for FF2 0–10000s 103 0
P10.14
1441 rw Set time for FF3
0–10000s 103 0
P10.15 1442 rw Set time for FF4 0–10000s 103 0
P10.16 1443 rw Set time for FF5 0–10000s 103 0
P10.17 1444 rw Set time for FF6 0–10000s 103 0
P10.18 1445 rw Set time for FF7 0–10000s 103 0