2.1.3 Configuration options
The CSI 9420 configuration options control the following operations:
• How measurement results are reported and how often are they reported
• The number and type of sensors installed
• How and when alerts are generated
Table 2-1 shows the default device configuration. You can change these configurations
from AMS Device Manager or from a Field Communicator.
Default device configurationTable 2-1:
Configuration option Default value
Publishing mode Generic
Update rate 60 minutes
PowerSave mode PowerSave Skip Multiplier of 1X
LCD mode Off
Power source Power module/battery
MHM Access Control Disabled
Write Protect No
Sensor Configuration
Sensor type 1 Accelerometer (sensor 2 not installed)
Sensor sensitivity 25 m V/g
Velocity Fmax 1000 Hz
PeakVue true Fmax 1000 Hz
Velocity spectrum lines of resolution 400 lines
PeakVue spectrum lines of resolution 1600 lines
Units
English
Overall velocity: in/s RMS
PeakVue: g's
Temperature: °C
Variable mappings
PV Overall velocity, sensor 1
SV PeakVue, sensor 1
TV Bias, sensor 1
QV Supply voltage
Configuration
12 MHM-97408, Rev 15