1592040000 XR70T EN v1.1 2019.07.09 XR70T 29/40
5th defrost starting time
0.0 to 23h50min(143); nu(144)
6th defrost starting time
0.0 to 23h50min(143); nu(144)
Restore default factory setting
9.6(0); 19.2(1);
38.4(2); 57.6(3);
Password for protected level Pr2
Probe P1 value visualization
Probe P2 value visualization
Probe P3 value visualization
Probe P4 value visualization
Real regulation Set Point (SET + ES +
SETd)
Firmware release date: day
Firmware release date: month
Firmware release date: year
The regulation is based on the temperature measured
by the thermostat probe (P1) with a positive differential
respect to the set point: if the temperature increases
and reaches the set point plus differential, the
compressor will start. The compressor will stop when
the temperature reaches the set point value again. In
case of fault because of the thermostat probe, the start
and stop of the compressor are timed through
parameters CoF and Con.
7. ENERGY SAVING
The standard SET-POINT (SET) is used to maintain the temperature at a certain value when the energy
saving status (ES) is not active. On the other hand, when the ES status is active a different SET-POINT
(SET_ES), higher than the standard one, will be used. The parameter HES defines the energy setpoint
according to the following formula: SET_ES = SET + HES
There are also two different differential values for SET and SET_ES, which are used for compressor cut-in
and cut-out: when ES status is active, the HYE parameter will be used instead of the HY parameter.
7.1 BASIC ENERGY SAVING ALGORITHM
The energy saving status will be always saved in the internal memory to resume previous operation if a
power failure occurs. The presence of a door switch to work properly (for example: i1F=dor) is required.