AO Function Block
December 2009
4-77
Table 4-24. Analog Output Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Setpoint Rate Down
SP_RATE_DN
18 ALL
Positive, 0 disables
rate limiting PV units
+INF
Data Type: Float
Ramp rate for downward set point changes.
When the ramp rate is set to zero, the set point is
used immediately.
Setpoint Rate Up
SP_RATE_UP
19 ALL
Positive, 0 disables
rate limiting PV units
+INF
Data Type: Float
Ramp rate for upward set point changes. When
the ramp rate is set to zero, the setpoint is used
immediately.
Setpoint High Limit
SP_HI_LIM
20 ALL PV Scale +/ 10% 100
Data Type: Float
The highest set point value allowed. SP_HI_LIM
must be greater than SP_LO_LIM.
Setpoint Low Limit
SP_LO_LIM
21 ALL PV Scale +/ 10% 0
Data Type: Float
The lowest set point value allowed. SP_LO_LIM
must be less than SP_HI_LIM.
AO Channel
CHANNEL
22 OOS 1=Setpoint 1=Setpoint
Data Type: Unsigned16
Defines which transducer parameter receives the
AO output. Select Setpoint to control valve
position.
Fault State Time
FSTATE_TIME
23 ALL Positive, seconds 0
Data Type: Float
Time from failure detection to reaction if failure
still exists.
Fault State Value
FSTATE_VAL
24 ALL PV Scale +/ 10% 0
Data Type: Float
Preset value to use if I/O_OPTS Fault State to
Value or Use Fault State Value on Restart is set.
Back Calculation Output
BKCAL_OUT
25 RO N/A
Status Limits
Dynamic
Data Type: DS-65
The value and status required by the BKCAL_IN
input of another block to prevent reset windup
and to provide bumpless transfer to closed loop
control.
Value
Remote Cascade Input
RCAS_IN
26 ALL
Status
BAD:
NoCom:
NoVal:
const
Data Type: DS-65
Target SP and status by supervisory host
Value 0 Trk
Shed Options
SHED_OPT
27 ALL
Defined by FF spec
0=Invalid
1=Normal Shed,
Normal Return
2=Normal Shed, No
Return
3=Shed to Auto,
normal return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
5=Shed to Manual,
normal return
6=Shed to Manual,
No return. Target
mode changes to
MAN on detection of
a shed condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)
0
Data Type: Unsigned8
Defines the action to be taken when the set point
is not updated in a remote mode.
Remote Cascade Output
RCAS_OUT
28 RO N/A
Status
Dynamic
Data Type: DS-65
Block set point and status after ramping
Value
Continued
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals