DVC6000f Digital Valve Controllers
December 2009
4-78
Table 4-24. Analog Output Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Update Event
UPDATE_EVT
29
Data Type: DS-73
This alert is generated by any changes to static
data.
UNACKNOWLEDGED 29.1 RW N/A
0:Undefined
1:Acknowledged
2:
Unacknowledged
0: Undefined
UPDATE_STATUS 29.2 RO N/A
0:Undefined
1:Update reported
2:Update not reported
0: Undefined
TIME_STAMP 29.3 RO N/A 0
STATIC_REVISION 29.4 RO N/A 0
RELATIVE_INDEX 29.5 RO N/A 0
Block Alarm
BLOCK_ALM
30
Data Type: DS-72
The block alarm is used for all configuration,
hardware, connection failure, or system problems
in the block.
UNACKNOWLEDGED 30.1 RW N/A
0:Undefined
1:Acknowledged
2:
Unacknowledged
0: Undefined
ALARM_STATE 30.2 RO N/A
0:Undefined
1:Clear reported
2:Clear not reported
3:Active reported
4:Active not reported
0: Undefined
TIME_STAMP 30.3 RO N/A 0
SUBCODE 30.4 RO N/A 0
VALUE 30.5 RO N/A 0
Extended Parameters
StdDev
STDDEV
31 RO N/A positive float Dynamic
Data Type: Float
Standard Deviation. To support DeltaV Variability
measurement.
Cap StdDev
CAP_STDDEV
32 RO N/A positive float Dynamic
Data Type: Float
Capability Standard Deviation. To support DeltaV
Variability measurement.
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals