Chapter 5 Use Of Monitoring Module M800D 81
5.5.4 Diesel Management Parameters
Parameter and alarm for diesel test
Table 1.1 Parameter and alarm for diesel test
Parameter Range Default Step change
Schedule Diesel Test Enabled Yes/No No N/A
Date of Schedule Diesel Test
Jan 1, 0 O’clock
Apr 1, 0 O’clock
Jul 1, 0 O’clock
Oct 1, 0 O’clock
Default category LED Alarm Number Alarm name
OA Y Diesel test in progress (Manual, or cyclic)
CA RED Diesel Generator Fault
5.5.5 Power Split Parameters
Table 1.1 Parameters of power split
Parameter Range Default Step change
Power Split Mode Master/Slave Master -
Current Limit Set Value 10 to 90% 60 1
Delta Voltage 0.1 to 2 V 0.5 0.1
Proportional Coefficient 0 to 10 2 0.1
Integral Time 1 to 2000 s 20 1