3 Installation
3.1 Overview
This section describes how to properly mount the Emerson Smart Wireless Gateway 1410
and make electrical connections, including electrical wiring, grounding, and host system
connections. This section also describes how to mount the optional remote antenna.
3.1.1 General considerations
The unit itself is not designed for outdoor mounting without a suitable enclosure. The
Gateway should be mounted in an approved electrical enclosure or building.
The Gateway should be mounted in a location that allows convenient access to the host
system network (process control network) as well as the wireless field device network and
protects the Gateway from moisture and contamination.
3.1.2
Physical description
The Gateway electronics is enclosed in a polymer housing. The front of the enclosure has
connections for power, Ethernet, and serial communications. The unit is designed to be
mounted on a DIN rail inside an electronic enclosure.
3.2 Mounting
The unit can be snapped onto a DIN TS35/7.5 or TS35/15 rail system. To clip the unit onto
the DIN rail, see Figure 3-1.
Procedure
1. Tilt the unit at a slight angle allowing the lower lip of the chassis to catch the
bottom of the DIN rail.
2. Apply pressure forward to snap the back of the unit securely onto the DIN rail.
Reference Manual Installation
00809-0200-4410 September 2020
Emerson.com/Rosemount 17