IQ8 Commercial Microinverter grid-tied PV system
18 © 2023 Enphase Energy Inc. All rights reserved. November 2023
USG-00026-1.0
Figure 7: QD Cable Clip
QD Sealing Caps
Cover any unused QD Cable connector with Enphase watertight QD Sealing Caps (QD-SEAL-10).
Listen for a click as the connectors engage.
Install QD Sealing Caps on all unused AC connectors because these connectors become live when
the system is energized.
QD Sealing Caps are required for protection against moisture ingress. Use the QD Disconnect Tool to
remove the QD Sealing Cap.
Figure 8: QD Sealing Cap
QD Terminator
Install the QD Terminator (QD-TERM-10) on any cut end of the QD Cable that is not connected to a
three-phase AC grid through a junction box or a three-phase field wireable connector.
Figure 9: QD Terminator
AC wire management at the junction box
The AC junction box can be used for feeding the AC connection to the microinverter branch circuit or
to splice two sections of QD Cable/Raw QD Cable together in case of complex installations with
multiple arrays across the rooftop. Follow these recommendations to prevent moisture from
accumulating in the AC junction box. This helps to improve system reliability while ensuring that the
wiring connections last for the life of the system.

Table of Contents

Other manuals for enphase IQ8H-3P-72-E-US

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the enphase IQ8H-3P-72-E-US and is the answer not in the manual?

enphase IQ8H-3P-72-E-US Specifications

General IconGeneral
Brandenphase
ModelIQ8H-3P-72-E-US
CategoryInverter
LanguageEnglish

Related product manuals