EasyManuals Logo

Fuji Electric FRENIC-Lift LM2A Series User Manual

Fuji Electric FRENIC-Lift LM2A Series
73 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
8-4
8.4.3 Leakage current of the EMC filter
This product has built-in EMC compliant filter that contains grounding capacitors for noise suppression which
increase the leakage current. Check whether there is no problem with electrical systems. When using this
product, the leakage current listed in Table 8.2 is added. Before adding this product, consider whether the
additional leakage current is allowable in the context of the overall system design.
Table 8.2 Leakage Current of FRENIC Lift
Input power
Inverter type
Leakage
current (mA)
Input power
Inverter type
Leakage
current (mA)
Three-phase
400 V
FRN0006LM2A-4
15
One-phase
200 V
FRN0011LM2A-7
15
FRN0010LM2A-4
FRN0018LM2A-7
FRN0015LM2A-4
FRN0019LM2A-4
FRN0025LM2A-4
FRN0032LM2A-4
FRN0039LM2A-4
3
FRN0045LM2A-4
FRN0060LM2A-4
8
FRN0075LM2A-4
FRN0091LM2A-4
* Calculated based on these measuring conditions
400V series: 400V, 50Hz with neutral grounding, and an interphase voltage unbalance ratio of 2%.
200V series: 230V, 50Hz with phase grounding.
Note: A box (") replaces an alphabetic letter depending on the shipping destination.
"Shipping destination: E (Europe) or A (Asia)

Table of Contents

Other manuals for Fuji Electric FRENIC-Lift LM2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric FRENIC-Lift LM2A Series and is the answer not in the manual?

Fuji Electric FRENIC-Lift LM2A Series Specifications

General IconGeneral
BrandFuji Electric
ModelFRENIC-Lift LM2A Series
CategoryInverter
LanguageEnglish

Related product manuals