5-80 D60 Line Distance Protection System GE Multilin
5.2 PRODUCT SETUP 5 SETTINGS
5
5.2.13 USER-PROGRAMMABLE PUSHBUTTONS
PATH: SETTINGS PRODUCT SETUP  USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1(16)
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic oper-
ands) into FlexLogic equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
USER PUSHBUTTON 1
PUSHBUTTON 1
FUNCTION: Disabled
Range: Self-Reset, Latched, Disabled
MESSAGE
PUSHBTN 1 ID TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 ON TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 OFF TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 HOLD:
0.0 s
Range: 0.0 to 10.0 s in steps of 0.1
MESSAGE
PUSHBTN 1 SET:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 RESET:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 AUTORST:
Disabled
Range: Disabled, Enabled
MESSAGE
PUSHBTN 1 AUTORST
DELAY: 1.0 s
Range: 0.2 to 600.0 s in steps of 0.1
MESSAGE
PUSHBTN 1 REMOTE:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 LOCAL:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
Range: 0 to 60.00 s in steps of 0.05
MESSAGE
PUSHBTN 1 LED CTL:
Off
Range: FlexLogic operand
MESSAGE
PUSHBTN 1 MESSAGE:
Disabled
Range: Disabled, Normal, High Priority
MESSAGE
PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled