6-10 D60 Line Distance Protection System GE Multilin
6.2 STATUS 6 ACTUAL VALUES
6
6.2.16 DIRECT DEVICES STATUS
PATH: ACTUAL VALUES STATUS  DIRECT DEVICES STATUS
These actual values represent the state of direct devices 1 through 16.
6.2.17 IEC 61850 GOOSE INTEGERS
PATH: ACTUAL VALUES  STATUS  IEC 61850 GOOSE UINTEGERS
The D60 Line Distance Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. See the Order Codes section in chap-
ter 2 for details.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
6.2.18 TELEPROTECTION CHANNEL TESTS
PATH: ACTUAL VALUES STATUS  TELEPROT CH TESTS
The status information for two channels is shown here.
DIRECT DEVICES
STATUS
DIRECT DEVICE 1
STATUS: Offline
Range: Offline, Online
MESSAGE
DIRECT DEVICE 2
STATUS: Offline
Range: Offline, Online
MESSAGE
DIRECT DEVICE 16
STATUS: Offline
Range: Offline, Online
IEC 61850
GOOSE UINTEGERS
UINT INPUT 1
0
MESSAGE
UINT INPUT 2
0
MESSAGE
UINT INPUT 16
0
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
Range: n/a, FAIL, OK
MESSAGE
CHANNEL 1 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
MESSAGE
CHANNEL 2
STATUS: n/a
Range: n/a, FAIL, OK
MESSAGE
CHANNEL 2 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
MESSAGE
VALIDITY OF CHANNEL
CONFIGURATION: FAIL
Range: n/a, FAIL, OK