6-28 D60 Line Distance Protection System GE Multilin
6.4 RECORDS 6 ACTUAL VALUES
6
PATH: ACTUAL VALUES RECORDS  PMU RECORDS PMU 1 RECORDING
6.4.6 BREAKER MAINTENANCE
PATH: ACTUAL VALUES  RECORDS  MAINTENANCE BREAKER 1(4)
There is an identical menu for each of the breakers. The BKR 1 ARCING AMP values are in units of kA
2
-cycles. Refer to the
COMMANDS  CLEAR RECORDS menu for clearing breaker arcing current records. The BREAKER OPERATING TIME is
defined as the slowest operating time of breaker poles that were initiated to open.
PMU 1
RECORDING
PMU 1 FORCE TRIGGER:
Yes
Range: No, Yes
MESSAGE
PUM 1 AVAILABLE
RECORDS: 0
Range: 0 to 65535 in steps of 1
MESSAGE
PUM 1 SECONDS
PER RECORD: 0.0
Range: 0 to 6553.5 in steps of 0.1
MESSAGE
PUM 1 LAST CLEARED:
2013/07/14 15:40:16
Range: date and time in format shown
BREAKER 1
BKR 1 ARCING AMP A:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP B:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP C:
0.00 kA2-cyc
MESSAGE
BKR 1 OPERATING TIME
A: 0 ms
MESSAGE
BKR 1 OPERATING TIME
B: 0 ms
MESSAGE
BKR 1 OPERATING TIME
C: 0 ms
MESSAGE
BKR 1 OPERATING
TIME: 0 ms