EasyManuals Logo
Home>GE>Protection Device>D60

GE D60 User Manual

GE D60
826 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #393 background imageLoading...
Page #393 background image
GE Multilin D60 Line Distance Protection System 5-259
5 SETTINGS 5.7 CONTROL ELEMENTS
5
Figure 5–134: EXAMPLE FLEXLOGIC CONTROL OF A SETTINGS GROUP
5.7.4 SELECTOR SWITCH
PATH: SETTINGS  CONTROL ELEMENTS  SELECTOR SWITCH SELECTOR SWITCH 1(2)
SELECTOR SWITCH 1
SELECTOR 1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
SELECTOR 1 FULL
RANGE: 7
Range: 1 to 7 in steps of 1
MESSAGE
SELECTOR 1 TIME-OUT:
5.0 s
Range: 3.0 to 60.0 s in steps of 0.1
MESSAGE
SELECTOR 1 STEP-UP:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 STEP-UP
MODE: Time-out
Range: Time-out, Acknowledge
MESSAGE
SELECTOR 1 ACK:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT A0:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT A1:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT A2:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 3BIT
MODE: Time-out
Range: Time-out, Acknowledge
MESSAGE
SELECTOR 1 3BIT ACK:
Off
Range: FlexLogic operand
MESSAGE
SELECTOR 1 POWER-UP
MODE: Restore
Range: Restore, Synchronize, Sync/Restore
MESSAGE
SELECTOR 1 TARGETS:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
SELECTOR 1 EVENTS:
Disabled
Range: Disabled, Enabled
10
1
VIRT IP 1 ON (VI1)
2
CONT IP 1 ON (H5A)
3
OR (2)
OR (2)
4
PHASE TOC1 PKP
5
NOT
6
PHASE TOC2 PKP
7
NOT
8
AND (3)
AND (3)
9
=VIRTOP1(VO1)
=VIRTOP1(VO1)
END