GE Multilin D60 Line Distance Protection System 5-265
5 SETTINGS 5.7 CONTROL ELEMENTS
5
5.7.5 TRIP OUTPUT
PATH: SETTINGS CONTROL ELEMENTS TRIP OUTPUT
TRIP OUTPUT
TRIP MODE:
Disabled
Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
MESSAGE
TRIP 3-POLE INPUT-1:
Off
Range: FlexLogic operand
MESSAGE
TRIP 3-POLE INPUT-2:
Off
Range: FlexLogic operand
MESSAGE
TRIP 3-POLE INPUT-6:
Off
Range: FlexLogic operand
MESSAGE
TRIP 1-POLE INPUT-1:
Off
Range: FlexLogic operand
MESSAGE
TRIP 1-POLE INPUT-2:
Off
Range: FlexLogic operand
MESSAGE
TRIP 1-POLE INPUT-6:
Off
Range: FlexLogic operand
MESSAGE
TRIP RECLOSE INPUT-1:
Off
Range: FlexLogic operand
MESSAGE
TRIP RECLOSE INPUT-2:
Off
Range: FlexLogic operand
MESSAGE
TRIP RECLOSE INPUT-6:
Off
Range: FlexLogic operand
MESSAGE
TRIP SEAL-IN DELAY:
0.000 s
Range: 0 to 65.535 s in steps of 0.001
MESSAGE
TRIP RESET:
CBaux OR Custom
Range: Pole Curr OR Custom, CBaux OR Custom,
Custom
MESSAGE
START TMR Z2PH Inp1:
Off
Range: FlexLogic operand
MESSAGE
START TMR Z2PH Inp2:
Off
Range: FlexLogic operand
MESSAGE
START TMR Z2GR Inp1:
Off
Range: FlexLogic operand
MESSAGE
START TMR Z2GR Inp2:
Off
Range: FlexLogic operand
MESSAGE
PHASE SELECTOR RESET
DELAY: 0.500 s
Range: 0.500 to 3.000 s in steps of 0.001 s
MESSAGE
TRIP FORCE 3-POLE:
Off
Range: FlexLogic operand
MESSAGE
TRIP PILOT PRIORITY:
0.000 s
Range: 0 to 65.535 s in steps of 0.001