GE Multilin D60 Line Distance Protection System 5-225
5 SETTINGS 5.6 GROUPED ELEMENTS
5
Figure 5–108: GROUND IOC1 SCHEME LOGIC
5.6.11 NEGATIVE SEQUENCE CURRENT
a) MAIN MENU
PATH: SETTINGS  GROUPED ELEMENTS SETTING GROUP 1(6)  NEGATIVE SEQUENCE CURRENT
The D60 relay provides two (2) negative-sequence time overcurrent elements, two (2) negative-sequence instantaneous
overcurrent elements, and two (2) negative-sequence directional overcurrent elements. For additional information on the
negative sequence time overcurrent curves, refer to the Inverse Time Overcurrent Curves section earlier.
NEGATIVE SEQUENCE
CURRENT
NEG SEQ TOC1
See page 5–226.
MESSAGE
NEG SEQ TOC2
See page 5–226.
MESSAGE
NEG SEQ IOC1
See page 5–227.
MESSAGE
NEG SEQ IOC2
See page 5–227.
MESSAGE
NEG SEQ DIR OC1
See page 5–228.
MESSAGE
NEG SEQ DIR OC2
See page 5–228.
SETTING
GROUND IOC1
FUNCTION:
Enabled = 1
SETTING
GROUND IOC1
SOURCE:
IG
GROUND IOC1
BLOCK:
Off = 0
FLEXLOGIC OPERANDS
GROUND IOIC DPO
GROUND IOC1 OP
SETTING
SETTING
IG PICKUP
GROUND IOC1
PICKUP:
RUN
GROUND IOC1 PICKUP
DELAY:
SETTINGS
GROUND IOC1 RESET
DELAY:
t
PKP
t
RST
827037A5.VSD
AND
GROUND IOC1 PKP