Maintenance
Intervention on the FK3- 4 operating device
GE Information L51- 303EN/05
8/10
11- 2016
Lubrication
Principl e
No future lubrication will be necessary. The bearings and rollers have been
lubricated in our workshops with special grease :
ASEOL SYLITEA 4- 018
This grease can easily endure very low temperatures and has an excellent
resistance to ageing. So that its qualities are not modified during use, it is
pro-
hibited to
:
D Mix this grease with any other lubricant.
D Lubricate later with any other oil.
D Spray parts of the apparatus with a protective liquid against corrosion or
with any kind of lubricating oil.
Mixture with other lubricants can cause the layer of grease to become too
hard.