Installation
Lifting and positioning the pole
GE Information08- 2016 L31- 200EN/07
3/4
Positioning the pole
Process
The table below gives the steps of positioning the pole :
Step Action
1 Use a lifting device to position the chassis frame onto its ground
attachment points but do not secure it
, whilst respecting the orient-
ation of the pole indicated on the sketch of the device
.
2 If necessary, place shims under the supports of the frame so that
the upper plate is level.
3 Install the washers (12) and clamp the whole to the ground using
nut.
4 Remove the lifting straps.
5
18 daN.m
Check the tightening torques of all frame screws.
6 T ighten the fixings on the two floor seatings in accordance with the
module entitled ’Tightening Torques and in accordance with the
diameters of the anchoring points.