BOILER SPECIFICATION 18sx
Lift weight 36kg (79Ib)
Total weight (installed) 41kg (90Ib)
Gas connection Ø O.D. 15mm. copper
Heating and return connection Ø O.D.
22mm. copper
Condensate connection Ø I.D.
21.5mm. plastic
Safety valve discharge connection Ø O.D. 15mm. copper
Safety valve (preset)
3 bar (43/5Ibf/in
2
)
Heating system minimum pressure 0.7bar (10.1Ibf/in
2
)
Maximum flow temperature 82°
Expansion vessel capacity
8 litres (1.76 gallons)
Expansion vessel charge pressure 0.5bar (7,3Ibf/in
2
)
Electrical supply 230V~50Hz
Electrical rating
180W fused 3A
IP clasification
X4D
Internal fuse rating on main PCB 2A
Gas supply (governed metre only)
I
2H
G20 natural gas
Inlet gas working pressure 20mbar
Burner % CO
2
case on 9.3 nominal
Burner % CO
2
case off 9.3 nominal
1.93 m
3
/hr
68.1 ft
3
/hr
0.99 m
3
/hr
35.1 ft
3
/hr
Approximate max. gas rate
after 10 mins. from cold
Approximate min. gas rate
after 10 mins. from cold
Heat input NETT Q = kW 18.2 max.
9.4 min.
Heat output P = kW
18.0 max.
9.3 min.
Flue type C
13, C33, C53
NOx Class 5
1 Technical Information
1.3 Gas Supply
The gas installation must be in accordance with the relevant
standards.
In GB this is BS6891.
In IE this is the current edition of I.S.813 “Domestic Gas
Installations”.
The supply from the governed meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg)
at the boiler.
On completion, test the gas installation for soundness using
the pressure drop method and suitable leak detection fluid,
purge in accordance with the above standard.
1.4 Technical Data
All dimensions are given in millimetres (except as noted).
See diagrams 1.1 and 1.2.
The data label is positioned on the base of the boiler.
13216
1.5 Condensate Drain
A plastic drain pipe must be fitted to allow discharge of
condensate to a drain.
Condensate should, if possible, be discharged into the internal
household draining system. If this is not practical, discharge
can be made externally into the household drainage system
or a purpose designed soak away, see section 8.2 for more
details.
1.6 Vertical Plumbing Kits
Should any combination of the domestic hot water, heating flow
or return pipes come from above the boiler, an Upward Piping
Kit is available to facilitate, part No. A2041500.
Contact Glow-worm for further details.
Diagram 1.2

Other manuals for Glow-worm Flexicom 18sx

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Glow-worm Flexicom 18sx and is the answer not in the manual?

Glow-worm Flexicom 18sx Specifications

General IconGeneral
BrandGlow-worm
ModelFlexicom 18sx
CategoryBoiler
LanguageEnglish

Related product manuals