EasyManuals Logo

Gree VERSATI III Series Service Manual

Gree VERSATI III Series
135 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
Unit Control
t (design temperature): generally it is 60°C ;
t (entering cold water temperature): it differs for different regions;
t ( water tank temperature set point): it is the target heating temperature of the water tank.
α: correction factor
Empirical Values for Volume Correction of the Water Tank
Duration of Use
(min/Person)
Flow Rate of the
Shower Head
(L/min)
10
15
20
25
30
40
4
0.48
0.71
0.94
1.18
1.42
1.89
6
0.71
1.06
1.42
1.77
2.12
2.83
8
0.95
1.42
1.89
2.36
2.83
3.77
10
1.18
1.77
2.36
2.95
3.54
4.72
15
1.76
2.65
3.54
4.42
5.31
7.08
Empirical values are worked out under conditions of 80L consumption (per day per person), 8L/min
flow rate of the shower head, and 10 minutes use duration per person.
7 Examples for Model Selection
7.1 General Introduction to the Example Project
For a two-floor house, there is a master room and a both room for each floor and both of them require
floor heating. Other rooms use the heat pump for heating in winter. The master room covers 28m
2
and
the both room covers 12m
2
.
7.2 Heat Load Calculation
7.2.1 Load Calculation of a Single Floor
Room
Area
Heat Index (W/m
2
)
Heat Load (W)
Master Room
28
82
2296
Bathroom
12
72
900
Total Load
2296+900=3196W
7.2.2 Arrangement Design of the Underfloor System for A Single Floor
Assumed conditions: the floor is cement or ceramics, the normal external diameter of the heating pipe
is 20mm, thickness of the stuffer is 50mm, thickness of PS foam insulation is 20mm, supply water
temperature is 45°C, return water temperature is 35°C, indoor design temperature is 20°C.
Average Temperature of the Heating Pipe=(45+35)/2=40°C
7.2.3 Arrangement Design of the Underfloor System for the Bath Room
Heat load of the bath room is 900W, heat dissipation per unit area is 75W/m
2
, tube spacing of the heat
pipe is 30mm, and heat loss is 25.4 W/m
2
, then the total heat loss is:
25.4×12=304.8W
Based on the heat load listed in the table above, the heating load for the bathroom is:
900+304.8=1204.8W
According to the formula Q=CρGΔT, the flow rate of the heating pipe for the bathroom is:

Table of Contents

Other manuals for Gree VERSATI III Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree VERSATI III Series and is the answer not in the manual?

Gree VERSATI III Series Specifications

General IconGeneral
TypeAir to Water Heat Pump
SeriesVERSATI III
RefrigerantR32
Operating Temperature Range (Cooling)10°C to 48°C
Heating Capacity4.0 - 16.0 kW
Cooling Capacity4.0 - 14.0 kW
COPUp to 4.5 (A7/W35)
EER3.2 - 4.3
Power Supply220-240V, 50Hz

Related product manuals