10.2 System fault
System fault (system faults are mainly caused by system instead of inverter, please check the
items as instructed below before replacing inverter).
Residual I High
Error: 201
1.Restart the invert.
2. If error message still exists, contact
Growatt.
PV Voltage High
Error: 202
The DC input voltage is exceeding
the maximum tolerable value.
1. Disconnect the DC switch immediately.
2. Check the voltage of each PV string
with multimerter.
3. If the voltage of PV string is lower than
550V, contact Growatt.
PV Isolation Low
Error: 203
1. Check if panel enclosure ground
properly.
2. Check if inverter ground properly.
3. Check if the DC breaker gets wet.
4. Check the impedance of PV (+) & PV (-)
between ground (must be more than 25 KΩ
or 550 KΩ(VDE 0126)). If the error message
is displayed despite the above checking
passed, contact Growatt.
Utility grid voltage is out of
permissible range.
Please switch off DC switch.
Check AC wiring, especially neutral and
ground wire.
Check grid voltage is complied with local
grid standard. Restart inverter, if problem
still exist, Contact Growatt.