44
Operation
If there is no communication between wired controller and
indoor unit for 4 minutes, it will display error code “07” when
checking malfunction.
Communication Malfunction of Wired Controller
If the dip switch is set to collect ambient Temp. from wired
controller and the sensor can’t work normally, it will display
error code “01” when checking malfunction.
Sensor Malfunction
(1) In OFF state, keep pressing key for 5 seconds, the
current temp. compensation value is displayed on the top-right
of the screen and ashes. “00” is the default value.
(2) When in celsius system, ambient compensation value is
-04~+04°C, while in fahrenheit system, ambient compensation
value being -07~+07°F. The temp. compensation value can be
adjusted by pressing
.
(3) After adjustment, press
 key to conrm the setting.
(4) The compensation value is used for ambient temp..
(5) The compensation value is valid only in the state of
collecting ambient temp. of wired controller.
Temp. Compensation Setting