EasyManuals Logo
Home>Honeywell>Control Panel>ESSER IQ8Control C

Honeywell ESSER IQ8Control C User Manual

Honeywell ESSER IQ8Control C
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15 71
7.1.3 Maximum line lengths based on the total load factor of a loop
FACP max. loop lenght Loop 1 Loop 2 Loop 3 Loop 4 Loop 5 Loop 6
IQ8Control M
up to 4 loops
up to 700 m 91 to 96 91 to 96 91 to 96 91 to 96 X X
800 m 85 to 90 85 to 90 85 to 90 85 to 90 X X
900 m 79 to 84 79 to 84 79 to 84 79 to 84 X X
1000 m 73 to 78 73 to 78 73 to 78 73 to 78 X X
1100 m 67 to 72 67 to 72 67 to 72 67 to 72 X X
1300 m 61 to 66 61 to 66 61 to 66 61 to 66 X X
1500 m 55 to 60 55 to 60 55 to 60 55 to 60 X X
1600 m 49 to 54 49 to 54 49 to 54 49 to 54 X X
2000 m 1 to 48 1 to 48 1 to 48 1 to 48 X X
2100 up to 3500 m 0 0 0 0 X X
IQ8Control M
up to 6 loops
up to 700 m 46 to 48 46 to 48 46 to 48 46 to 48 46 to 48 46 to 48
800 m 43 to 45 43 to 45 43 to 45 43 to 45 43 to 45 43 to 45
900 m 40 to 42 40 to 42 40 to 42 40 to 42 40 to 42 40 to 42
1000 m 37 to 39 37 to 39 37 to 39 37 to 39 37 to 39 37 to 39
1100 m 34 to 36 34 to 36 34 to 36 34 to 36 34 to 36 34 to 36
1300 m 31 to 33 31 to 33 31 to 33 31 to 33 31 to 33 31 to 33
1500 m 28 to 30 28 to 30 28 to 30 28 to 30 28 to 30 28 to 30
1600 m 25 to 27 25 to 27 25 to 27 25 to 27 25 to 27 25 to 27
2000 m 1 to 24 1 to 24 1 to 24 1 to 24 1 to 24 1 to 24
2100 up to 3500 m 0 0 0 0 0 0
7.1.4 Technical Data loop module
Part No. 784382 / 784382.10 /
784382.D0 (esserbus
®
)
Part No. 804382 / 804382.10 /
804382.D0 (esserbus
®
PLus)
Internal voltage supply Internal +12 V and +27,5 V Internal +12 V and +42 V
Quiescent current
(with 127 loop devices)
60 mA @ 12 V 60 mA @ 12 V
Emergency operation yes yes
Terminals removable, for max. 1,5 mm
2
Recommended connecting
cable
Telephone cable I-Y (ST) Y n x 2 x 0.8mm with special designation or
fire detection cable
Loop resistance 65 @ 1000 m loop length
(measured from terminal A+ to B+)
Total loop resistance max. 130 (measured from terminal A+ to B+)
Up to 3500 m total loop length is possible for IQ8 fire detectors or alarm
devices with consideration of the load factor
The permitted loop length depends on the number and type of the loop devices and may differ
from the max. loop length.
max. 2 loop modules Part No. 804382 / 804382.10 / 804382.D0 per IQ8Control C as well as max.
4 or 6 modules per IQ8Control M
Part No. 784382 / 784382.10 / 784382.D0 loop module (esserbus
®
) loop module to connect
fire detectors and esserbus
®
-transponder. The required loop voltage 27.5 V must be selected via
the jumper on the power supply module Part No. 802426 of the FACP
Part No. 804382 / 804382.10 / 804382.D0 loop module (esserbus
®
-PLus)
loop module to connect Fire detectors and esserbus
®
-transponder and alarm devices. The
required loop voltage 42 V must be selected via the jumper on the power supply module (Part No.
802426) of the FACP.
Do not exceed the max. admissible total load factor of 96 (per loop)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ESSER IQ8Control C and is the answer not in the manual?

Honeywell ESSER IQ8Control C Specifications

General IconGeneral
BrandHoneywell
ModelESSER IQ8Control C
CategoryControl Panel
LanguageEnglish

Related product manuals